Chongqing Gold Mechanical & Electrical Equipment Co., Ltd.
Products
Contact Us
  • Contact Person : Ms. ren pan
  • Company Name : Chongqing Gold Mechanical & Electrical Equipment Co., Ltd.
  • Tel : 86-23-62940053
  • Fax : 86-23-62940030
  • Address : Chongqing,Chongqing,9/F-10, Jingtai Building, NAN AN DISTRICT, CHONGQING
  • Country/Region : China
  • Zip : 400060

GDCR-602 Re-firing Circuit Breaker Instrument

GDCR-602 Re-firing Circuit Breaker Instrument
Product Detailed
Related Categories:Circuit Breakers
GDCR-602 Re-firing Circuit Breaker Tester can test the vacuum circuit breakers which be used to switch capacitor groups.

1.1General introduction

GDCR-602 Re-firing Circuit Breaker Instrument is designed to test the vacuum circuit breakers which be used to switch capacitor groups. 

It records three phase and neutral point voltage and three phase current of capacitor groups in high frequency 

when vacuum circuit breaker open and close capacitor to the grid. 

The tester can inspect whether there is a reconnect procedure when circuit breaker open the connection of

capacitor and grid. If there is a reconnection the tester will find the maximum voltage value and the reconnect phase.

GDCR602 test set include four high frequency response dividers which are installed to the three phase lines and 

neutral points to measure the voltage capacitor groups. GDCR602 is based on new DSP and embedded 

computer technology. 12.1 TFT LCD is designed for data display. All the sample channels are isolated to each 

other. The main box of GDCR602 could be used as a signal recorder. It has a extensive processing software. 

The data process software include automatic power generator test template, signal recorder test template,

power quality analysis, spectrum analysis tools, flexible figure tools and so on.

1.2 Functions

1.The maximum current detection and signal recorder in vacuum circuit breakers close capacitor group procedure.

2.The reconnect detection and maximum voltage measurement in vacuum circuit breakers open procedure. 

3 Transient signal recorder

4 Power generator no-loader characteristics

5 Power generator short characteristics

6 Power generator excitation system test

7 Power quality analysis test

8 Spectrum analysis tools

9 Flexible figure draw tools

10 Harmonic analysis tools

11 Graphics analysis such as zoom, positioning, compute and so on

12 Make word and excel test report automatic

1.3 Technique index

1. All channels isolate each other

2 Voltage and current  measure range:

-400V¬400V,-200V¬200V,-10V¬10V, -20mA¬20mA

3 High voltage dividers range: 0~50KV error 1%, frequency response range:500KHz

4 Ratio of high voltage dividers: 1000:1

5 Measurement errors of main box:

-400V¬400V             <0.5V

-200V¬200V             <0.2V

-10V¬10V                <0.01V

-20mA¬20mA             <0.02mA

6 5 switch signal input nodes, 12 analog signal input nodes

7 Power supply AC220V ±10%, 50Hz

8 Power dissipation <60W

9 Work temperature 0¬50 °C, Humidity: ≤90%RH

GDCR-602 Re-firing Circuit Breaker Instrument



Copyright Notice @ 2008-2022 ECBAY Limited and/or its subsidiaries and licensors. All rights reserved.